We represent Instrument Transformer Technologies Ltd of South Africa, ITT is the largest manufacturer of the Southern Hemisphere of Instrumentation Transformers, a company with presence in Asia, Australia and America, is known for its very high quality products in line with the high prestige of South Africa as A manufacturing of engineering products is concerned, ITT has IEC and ISO9001 certifications. ITT’s products and services offer includes the manufacture of current and voltage transformers (from 3.3kV to 132kV) and measurement units from 6.6kV- 33kV for pole and ground mounted applications.
Auri Business is the exclusive representative of ITT and helps you select the best equipment for your project, all payments are made 100% directly to our represented company without increasing any commercial margin, and we as an Auri Business can optionally handle all the logistics and processes Customs from the departure of their transformers from South Africa to the delivery at the door of your company, we are aware of the local legislation regarding the importation of electrical equipment in general in each country we represent and it is very certain that the prices you can get with We for the purchase of their transformers are unbeatable.
ITT products are aimed exclusively at electricity transmission or distribution generating companies, as well as large consumers of energy such as mining, shopping centers, large industry among others, which, due to their business activity, require the measurement of electrical parameters in HIGH VOLTAGE up to 132KVThe countries where we represent ITT exclusively are: Peru, Chile, Colombia, Ecuador, Bolivia.

PRODUCTS
SPECIFICATIONS
Nominal Voltage Un | kV | 11 | 22 | 33 |
Highest System Voltage Um | kV | 12 | 24 | 36 |
Lightning Impulse (BIL) | kV | 95 | 150 | 200 |
Power Frequency Withstand (60s) | kV | 28 | 50 | 70 |
Specification | IEC 60044-1 / 2 | |||
Insulation Medium | Paper / Oil | |||
Bushings // Creepage | mm/kV | Porcelain// Composite (Very High Pollution) | ||
Terminal | mm | 26 x 125 or 38 x 125 | ||
Tank Finish | Zinc sprayed, Red Oxide undercoat, 2 x Enamel Final coat | |||
Class | Metering and Protection | |||
Current Ratio | As per Customer specifications |

Nominal Voltage Un | kV | 11 | 22 | 33 |
---|---|---|---|---|
Highest System Voltage Um | kV | 12 | 24 | 36 |
Lightning Impulse (BIL) | kV | 95 | 150 | 200 |
Power Frequency Dry (60s) | kV | 28 | 50 | 70 |
Specification | IEC 60044-1 & IEC 60044-2 & IEC 60044-3 | |||
Rated Current | A | 10 to 600 | ||
Short Time Current for 1 Second | kA | 4 to 20 | ||
Insulation Medium | Paper/Oil | |||
Bushings / Creepage | mm/kVA | 31 (Very Heavy Pollution) | ||
Terminals | mm | M12 x 35 | M14 x 52 | M20 x 60 |
Tank Finish | Zinc sprayed, Red Oxide undercoat, 2 x Enamel final coat. | |||
VT Ratio Primary | V | 11000 | 22000 | 33000 |
VT Ratio Secondary | V | 110 or 220 | ||
VT Burden | VA | 25 to 200 | ||
VT Class | 0.2/0.5 | |||
Voltage Factor | 1.9 | |||
VT Core | 3 Phase 3 Limb or 3 Phase 5 Limb | |||
CT’s / Unit | 2 or 3 Phases / Up to 2 per Phase | |||
CT Ratio Primary | A | 10-20-30-40-50-60 or 50-100-150-200 or 150-200-250-300-400-500-600 | ||
CT Ratio Secondary | A | 1-2-5 | ||
CT Burden | VA | 1 – 10 | ||
CT Class | 0.2S/0.2/0.5 |

Resin Encapsulated Voltage Transformer
Resin Encapsulated
VOLTAGE TRANSFORMERS
SPECIFICATIONS
Kv | Ratio | VA | Class | VF |
---|---|---|---|---|
3.3 | 3300:110 | 50 | 0.2 | 1.9 |
3.3 | 3300:110 | 100 | 0.5 | 1.9 |
3.3 | 3300:110 | 200 | 1 | 1.9 |
3.3 | 3300:110 | 400 | 3 | 1.9 |
3.3 | 3300:110 | 1000 | 5% | 1.2 |
Kv | Ratio | VA | Class | VF |
---|---|---|---|---|
6.6 | 6600:110 | 50 | 0.2 | 1.9 |
6.6 | 6600:110 | 100 | 0.5 | 1.9 |
6.6 | 6600:110 | 200 | 1 | 1.9 |
6.6 | 6600:110 | 400 | 3 | 1.9 |
6.6 | 6600:110 | 1000 | 5% | 1.2 |
Kv | Ratio | VA | Class | VF |
---|---|---|---|---|
11 | 11000:110 | 50 | 0.2 | 1.9 |
11 | 11000:110 | 100 | 0.5 | 1.9 |
11 | 11000:110 | 200 | 1 | 1.9 |
11 | 11000:110 | 400 | 3 | 1.9 |
11 | 11000:110 | 1000 | 5% | 1.2 |
3 Phase 5 Limb | ||||
---|---|---|---|---|
Kv | Ratio | VA | Class | VF |
3.3 | 3300:110-63.5 | 100-50 | 1-3P | 1.9 |
6.6 | 6600:110-63.5 | 100-50 | 1-3P | 1.9 |
11 | 11000:110-63.5 | 100-50 | 1-3P | 1.9 |

SPECIFICATIONS
Nominal Voltage Un | kV | 6.6 | 11 | 22 |
---|---|---|---|---|
Highest System Voltage Um | kV | 7.2 | 12 | 24 |
Lightning Impulse (BIL) | kV | 60 | 95 | 150 |
Power Frequency Dry (60s) | kV | 20 | 28 | 50 |
Specification | IEC 60044-1 & IEC 60044-2 & IEC 60044-3 | |||
Insulation Medium | Paper / Oil | |||
Bushings (*on specific designs) | Resin suitable for *dead break or taped cable connections | |||
Fuses (*on specific designs) | HV* under oil and LV | |||
Metering Cubicle (on specific designs) | Test Block, VT Live LED Indicator, and provision for Energy meter | |||
Tank Finish | Zinc sprayed, Red Oxide undercoat, 2 x Enamel final coat | |||
VT Ratio Primary | V | 6600 | 11000 | 22000 |
VT Ratio | V | 110 or 220 | ||
VT Burden | VA | 25 to 200 | ||
VT Class | 0.2/0.5 | |||
Voltage Factor | 1.9 | |||
VT Core | 3 Phase 3 Limb or 3 Phase 5 Limb | |||
CT’s / Unit | 2 or 3 Phases / Up to 2 per Phase | |||
CT Ratio Primary | A | 10-20-30-40-50-60 or 50-100-150-200 or 150-200-250-300-400-500-600 | ||
CT Ratio Secondary | A | 1 – 5 | ||
CT Burden | VA | 1 to 10 | ||
CT Class | 0.2S/0.2/0.5 |